A low power factor can increase electricity costs for factories, commercial buildings and other eligible TNB customers. In 2026, the TNB power factor penalty is a surcharge linked to how efficiently a premises uses electrical capacity. Your meter may also record kVARh, the reactive energy associated with equipment such as motors and transformers. However, a kVARh reading does not automatically mean a separate kVARh tariff applies.

This guide explains the relevant thresholds, how the power factor surcharge is calculated, where to check your bill and how suitable correction equipment may help.

1.Power Factor Penalty at a Glance

The TNB power factor penalty is a surcharge imposed on eligible customers whose measured power factor falls below the prescribed threshold. In 2026, the applicable threshold depends on the electricity supply voltage. The table below summarises the main requirements for commercial and industrial customers.

Customer categoryPower factor thresholdSurcharge rate
Eligible LV commercial and MV customers (below 132 kV)Below 0.85 to 0.751.5% per 0.01 below 0.85
Same categoryBelow 0.75Additional 3% per 0.01 below 0.75
Customers supplied at 132 kV and aboveBelow 0.90Applicable high-voltage surcharge
Domestic and streetlight tariffsExemptNo surcharge

The surcharge is calculated using the applicable electricity charges, including energy, demand and AFA components. Maintaining a satisfactory power factor helps customers avoid additional electricity costs.

2.What Is Power Factor?

Power factor measures how effectively electrical power is used. It is expressed as a ratio from 0 to 1, where 1 represents ideal efficiency in the use of apparent power. A power factor of 0.95 means that 95% of apparent power is converted into active power.

TermMeaningCommon application
kW (active power)Power used to perform useful workMotors, lighting and equipment
kVAR (reactive power)Power exchanged through electrical and magnetic fieldsMotors and transformers
kVA (apparent power)Combined magnitude of active and reactive powerElectrical equipment sizing
Maximum demand (MD)Highest average kW demand recorded over a billing intervalDemand-based electricity charges

A lower power factor requires greater current to deliver the same useful power, increasing electrical system loading. Improving power factor can reduce reactive power demand and help avoid TNB surcharges. However, it does not necessarily reduce billed maximum demand, which is generally measured in kW over a 30-minute interval.

3.What Is kVARh and Why Does TNB Charge for It?

kVARh stands for kilovolt-ampere reactive hours and measures reactive energy consumed over time. Unlike kW (active power), which performs useful work, kVAR (reactive power) supports the magnetic and electric fields required by equipment such as motors, transformers and air-conditioning systems. kVARh measures the accumulated reactive energy used over a period.

TNB meters may record both active energy (kWh) and reactive energy (kVARh). These readings help assess a customer’s power factor, which indicates how effectively electrical capacity is utilised.

Under TNB’s power factor surcharge framework, eligible customers may incur additional charges when their measured power factor falls below the applicable threshold. However, recording kVARh does not automatically result in a separate charge for each unit of reactive energy.

During Regulatory Period 4 (RP4), from 1 July 2025 to 31 December 2027, electricity tariffs in Peninsular Malaysia operate under the revised tariff structure and monthly Automatic Fuel Adjustment (AFA) mechanism. TNB calculates applicable power factor surcharges using specified electricity charges, including relevant kWh, kW and AFA components.

For example, if a meter records 10,000 kWh and 6,000 kVARh over the same period, the approximate power factor is:

This simplified calculation assumes sinusoidal electrical conditions. Actual billing assessments depend on TNB’s metering methodology.

Regularly monitoring kVARh readings alongside electricity consumption can help businesses identify potential power factor issues and opportunities to improve electrical efficiency.

4.TNB Power Factor Surcharge Rates 2026

For eligible customers supplied below 132 kV, TNB imposes a power factor surcharge when the measured power factor falls below 0.85. The surcharge increases progressively as the power factor decreases.

Power factor (PF)Surcharge rate
0.85 and aboveNo surcharge
Below 0.85 to 0.751.5% for every 0.01 below 0.85
Below 0.7515% for the first reduction from 0.85 to 0.75, plus 3% for every additional 0.01 below 0.75

For example, a power factor of 0.80 attracts a 7.5% surcharge, while a power factor of 0.70 attracts a 30% surcharge.

The surcharge applies to the relevant electricity charges, including applicable kWh, kW and Automatic Fuel Adjustment (AFA) components, rather than necessarily the total invoice amount.

Customers supplied at 132 kV and above are subject to a higher minimum power factor requirement of 0.90. Maintaining the prescribed power factor helps businesses avoid additional electricity costs.

5.How to Find the Power Factor Penalty on Your TNB Bill

You can check for a power factor penalty or surcharge by reviewing your TNB electricity bill or detailed metering statement. The information displayed may vary depending on your tariff category, supply voltage and meter type.

Look for the following details:

  • Tariff category: Identify whether your premises receives low-voltage (LV), medium-voltage (MV) or high-voltage (HV) supply.
  • Power factor (PF): Check the recorded power factor to determine whether it falls below TNB’s applicable threshold.
  • Meter readings: Review electricity consumption (kWh), reactive energy (kVARh) and maximum demand (kW), where available.
  • Surcharge: Look for a power factor surcharge under the applicable billing charges.
  • Billing period: Compare readings across different months to identify changes in electricity usage.

Illustrative Example of Electricity Billing Details on a TNB Bill:

Active energy (kWh)10,000 kWh
Reactive energy (kVARh)8,000 kVARh
Power factor (PF)0.78
Power factor surchargeRM1,050*

*Illustrative surcharge assuming a RM10,000 applicable charging base and a 10.5% surcharge rate for PF 0.78.

A kVARh reading alone does not automatically result in a surcharge. If your bill does not display the relevant readings, contact TNB for clarification or request the available detailed metering information. Regular monitoring can help businesses identify power factor issues and manage electricity costs.

6.Worked Example: Factory with PF 0.78

Aerial view of an industrial estate in Malaysia with rooftop solar panels on the factory buildings

Consider a factory supplied below 132 kV with a monthly power factor of 0.78. Assume its applicable electricity charges, comprising energy (kWh), demand (kW) and Automatic Fuel Adjustment (AFA) components, total RM10,000 per month.

The table below illustrates the TNB power factor penalty and potential savings from improving the power factor to 0.95.

CalculationIllustrative result
Monthly electricity charges before power factor surchargeRM10,000
Recorded power factor0.78
Shortfall below 0.850.07
Surcharge rate7 × 1.5% = 10.5%
Monthly power factor surchargeRM10,000 × 10.5% = RM1,050
Total monthly charges including surchargeRM11,050
Power factor after correction0.95
Monthly surcharge after correctionRM0
Potential annual savingsRM1,050 × 12 = RM12,600
RM12,600per year
Potential annual savings

By improving its power factor from 0.78 to 0.95, the factory could eliminate the surcharge and save RM12,600 annually.

By improving its power factor from 0.78 to 0.95, the factory could eliminate the surcharge and save RM12,600 annually, assuming electricity usage, applicable charges and operating conditions remain unchanged.

These savings represent avoided surcharge costs, rather than a reduction in electricity consumption. Actual net savings depend on equipment installation, maintenance and operating costs.

Power factor correction may also reduce electrical losses and improve system capacity. However, it does not necessarily reduce billed maximum demand measured in kW. Businesses should assess their electricity usage and billing records before investing in corrective equipment.

7.How to Fix Low Power Factor

Avera engineer in a safety vest testing a power factor controller reading 0.96 lag inside an open capacitor bank cabinet

To reduce the risk of a power factor penalty, businesses can consider suitable correction equipment, inverter settings and better load management. The appropriate solution depends on your facility’s electrical demand and operating conditions.

Capacitor Banks

A capacitor bank is commonly used to improve lagging power factor in commercial and industrial facilities. Fixed capacitor banks suit relatively stable loads, while automatic capacitor banks adjust reactive power compensation as electricity demand changes.

In Malaysia, smaller fixed capacitor bank installations may cost approximately RM5,000 – RM20,000, depending on capacity, equipment specifications and installation requirements. Larger automatic systems or those requiring harmonic filtering may cost more.

Payback depends on installation costs and avoided surcharges. For example, a system costing RM10,000 that eliminates a monthly surcharge of RM1,050 could achieve a simple payback of approximately 10 months, excluding maintenance and operating costs.

Correct sizing is essential to prevent overcompensation, harmonic resonance and equipment damage.

Solar Inverters with Reactive Power Support

Certain solar inverters can supply or absorb reactive power to help manage power factor, subject to their technical capabilities and applicable grid requirements.

However, installing solar panels does not automatically improve power factor. Where solar generation reduces grid-imported active power while reactive demand remains unchanged, the power factor recorded by TNB may deteriorate.

Suitable inverter settings should therefore be assessed alongside existing capacitor banks, site demand and applicable TNB connection requirements.

Load Audit

A load audit helps identify the causes of low power factor and opportunities for improvement. It typically examines:

  • Electricity consumption, reactive energy (kVARh) and maximum demand.
  • Motor and transformer loading, including inefficient operating patterns.
  • Existing capacitor banks, harmonics and power factor trends.

Following the assessment, corrective measures may include equipment upgrades, load scheduling, capacitor bank installation or inverter adjustments.

Explore Avera Energy’s Operations & Maintenance Services to learn how monitoring, energy audits and ongoing system management can help improve electrical performance.

8.Frequently Asked Questions (FAQ)

TNB requires a minimum power factor of 0.85 for electricity supplies below 132 kV and 0.90 for supplies at 132 kV and above. Maintaining a power factor of 0.95 or higher is a practical target that provides additional margin against potential surcharges. Regular monitoring helps businesses maintain consistent electrical performance.

kVARh measures reactive energy used by electrical equipment over time. TNB meters may record kVARh alongside active electricity consumption (kWh). However, recording kVARh does not automatically mean a separate charge applies. TNB’s power factor surcharge depends on the measured power factor and applicable billing charges, rather than a universal fixed rate per kVARh.

For eligible supplies below 132 kV, TNB charges 1.5% for every 0.01 below a power factor of 0.85, with an additional 3% for every 0.01 below 0.75. For example, a power factor of 0.78 attracts a 10.5% surcharge on the applicable electricity charges, including relevant energy, demand and AFA components.

Not necessarily. Solar panels reduce grid electricity consumption but do not automatically improve power factor. Where reactive power demand remains unchanged, increased solar generation may reduce the power factor measured at the grid connection. Compatible solar inverters can provide reactive power support when appropriately configured, subject to applicable technical and grid connection requirements.

Yes. Commercial shops and other eligible non-domestic premises may incur a power factor surcharge when their measured power factor falls below TNB’s prescribed threshold. This can apply even to low-voltage commercial accounts. Customers should check their electricity bills, tariff category and power factor readings to determine whether a surcharge applies.

Payback depends on equipment costs, installation requirements and the power factor penalties that can be avoided. For example, a capacitor bank costing RM10,000 that eliminates a monthly surcharge of RM1,050 would have a simple payback of approximately 10 months. Actual payback varies with electricity usage, equipment performance, maintenance costs and operating conditions.

9.Get a Free Power Factor Check

Send us your TNB electricity bill and let us check your power factor for free

Simply share a recent commercial or industrial electricity bill with Avera Energy. Our team will review your power factor, identify potential surcharges and explore opportunities to reduce your electricity costs.

Contact Avera Energy today
for a complimentary initial assessment and discover how we can help improve your facility's energy efficiency.

Other Articles

Two Avera Energy engineers in safety vests and helmets inspecting a commercial rooftop solar system beside an inverter, one holding a tablet

Solar Panel Maintenance in Malaysia: Cost, Schedule and O&M Guide for Commercial Systems (2026)

Aerial view of a ground-mounted solar farm with a grid substation, surrounded by green hills

Renewable Energy Certificates (REC) in Malaysia: mREC, I‑REC and How to Buy Them (2026)